Title: Identification of Various Internal Faults of Transformer Based on No-load Current Analysis
Authors: Desai, Rushi R.
Patel, Amit N.
Gupta, Vinod R.
Keywords: Transformer Internal Faults
%THDi
No-load Current Analysis
Harmonics
Electrical Faculty Paper
Faculty Paper
ITFEE012
Issue Date: Feb-2012
Publisher: IJETAE
Series/Report no.: ITFEE012-2
Abstract: The internal faults of transformer can be identified by various techniques. The proposed technique is by the analysis of no-load current and harmonic contents present in it. The no-load current of transformer is non-sinusoidal for sinusoidal input voltage. And hence it contains harmonics in healthy condition of transformer. But if transformer has any internal fault then the no-load current magnitude and its harmonic content will vary depending upon the type of fault. The winding fault increases the %THDi and magnitude of no-load current, whereas the core fault increases only the %THDi of no-load current. For winding fault if the inter-turn fault is on the primary side then both %THDi and magnitude of no-load current increases but if the inter-turn fault is on secondary side then only magnitude of no-load current will increase.
Description: International Journal of Emerging Technology and Advanced Engineering (IJETAE), Vol. 2 (2) February, 2012
URI: http://10.1.7.181:1900/jspui/123456789/3260
ISSN: 2250-2459