Please use this identifier to cite or link to this item: http://10.1.7.192:80/jspui/handle/123456789/5499
Title: Comparative Study of The Effect of Different Gate Firing Schemes on the Operation of a Prototype HVDC Transmission System
Authors: Siddiqui, Mohammedirfan
Bhatt, Chanakya
Keywords: High Voltage Direct Current Transmission (HVDC)
Individual Phase Control (IPC) Scheme
Equidistant Pulse Control (EPC) Scheme
Phase Locked Loop (PLL)
Thyristor Bridge Converters
Electrical Faculty Paper
Faculty Paper
ITFEE024
NUiCONE
NUiCONE - 2013
Issue Date: 2013
Publisher: IEEE
Citation: 4th International Conference on Current Trends in Technology, NUiCONE - 2013, Institute of Technology, Nirma University, November 28 – 30, 2013
Series/Report no.: ITFEE024-1;
Abstract: Two high voltage direct current transmission line circuits have been simulated in the PSIM software, one employing the Individual Phase Control scheme and the other, Equidistant Pulse Control scheme. This paper presents the circuitry employed in the two simulations and the results obtained from both. It is shown that the circuit employing the former scheme suffers from an excess of non-characteristic harmonics when operating with a weak AC system whereas the latter can work on weak AC systems without problems of harmonic instability because it generates firing pulses independent of the AC source. The implementation of the two schemes clearly demonstrates how one is dependent on the feedback from the source whilst the other utilizes a Phase Locked Loop to circumvent this problem.
URI: http://hdl.handle.net/123456789/5499
Appears in Collections:Faculty Papers, EE

Files in This Item:
File Description SizeFormat 
ITFEE024-1.pdfITFEE024-1281.77 kBAdobe PDFThumbnail
View/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.