Title: | Implementation of Anti-Islanding Scheme for a Grid Connected Inverter |
Authors: | Saikia, Arupkumar Kapil, P. N. |
Keywords: | Active Islanding Method Active Frequency Drifts Method Distributed Generation Electrical Faculty Paper Faculty Paper ITFEE021 |
Issue Date: | Jan-2015 |
Publisher: | Springer India |
Citation: | Implementation of Anti-Islanding Scheme for a Grid Connected Inverter”, Power Electronics and Renewable Energy Systems, January, 2015, Chapter - 22, Page No. 213-223 |
Series/Report no.: | ITFEE021-12; |
Abstract: | As more PV systems join the utility grid the concern of undetected islanding operation increases. This concern is due to the safety hazards this phenomenon imposes on personnel and equipment. This paper discusses there different islanding schemes used and their features. As AFD method is the most popular method of islanding detection this paper proposes an improved method, where it uses AFD scheme for islanding detection but keeps the power quality high and the current THD less than 5 %. Also the paper shows the effectiveness in detecting island in less than 2 s according to IEEE standards. |
URI: | http://hdl.handle.net/123456789/6360 |
ISBN: | 978-81-322-2118-0 |
ISSN: | 978-81-322-2119-7 (Online) |