Title: Multiphysics Analysis of Isolator Contact under Steady State and Short Circuit Condition
Authors: Dholiya, Harshidaben Bharatbhai
Keywords: Electrical 2017
Project Report 2017
Electrical Project Report
Project Report
17MEE
17MEEE
17MEEE03
EPS
EPS 2017
EE (EPS)
Electrical Power Systems
Issue Date: 1-Jun-2019
Publisher: Institute of Technology
Series/Report no.: 17MEEE03;
Abstract: It is essential to know the forces acting on contacts of Isolator to achieve optimal mechanical oper- ation at the stage of designing. A major contribution is provided by the magnetic force associated with current constriction close to the small regions where electrical contact is provided. This cur- rent constriction is dependent on the actual resistance between two contacts. The actual resistance between two contacts known as contact resistance is function of contact force, contact area and hardness of contact material. Due to current constriction, temperature increases at contact surface which leads to overheating, thermal stress and deformation of contact and may damage contact permanently. The steady state temperature rise, Dynamic forces and temperature rise behaviour under short- circuit condition are important for reliable electric contacts. Decoupled electromagnetic and thermal analysis cannot give proper results, as contact resistance changes with temperature. The electromagnetic force is significant during short circuit condition which is omitted in mechanical, electrical and thermal coupled field analysis. Mechanical behaviour of the contact is also very important which is not considered during electromagnetic-thermal coupled FEM analysis. Considering all these effects, a 3-D coupled field finite element (FE) model of isolator is essential to predict its performance in steady state as well as short circuit condition. Electromagnetic forces and temperature can be derived using electromagnetic-thermal coupled analysis. These temperature and forces are used in thermal-mechanical coupled field analysis as an input. This coupled field analysis can be used to find temperature rise and electromagnetic forces which may cause deformation of isolator.
URI: http://10.1.7.192:80/jspui/handle/123456789/9005
Appears in Collections:Dissertation, EE (EPS)

Files in This Item:
File Description SizeFormat 
17MEEE03.pdf17MEEE032.26 MBAdobe PDFThumbnail
View/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.