Please use this identifier to cite or link to this item: http://10.1.7.192:80/jspui/handle/123456789/9405
Title: Improvement in Overload Performance of MCCB at Minimum Setting of Thermal Knob
Authors: Pandya, Khanjan Vijaykumar
Keywords: Electrical 2018
Project Report 2018
Electrical Project Report
Project Report
18MEE
18MEEE
18MEEE07
EPS
EPS 2018
EE (EPS)
Electrical Power Systems
Issue Date: 1-Jun-2020
Publisher: Institute of Technology
Series/Report no.: 18MEEE07;
Abstract: Moulded Case Circuit Breakers (MCCB) is short circuit protecting device which is used for short circuit and overload protection. It is used in Industries, Commercial, Institutional buildings, Electrical Machines protection against short circuit condition and overload condition. This project focuses L&T MCCB having current rating from 20 A to 100 A. The scope of this project is to improve a reliability of MCCB in terms of thermal (overload) performance in minimum setting of thermal knob as per IEC 60947-2 standard. L&T MCCB has (0.8- 1)×Iƞ variable setting of the overload release i.e. 100 A rated MCCB can be de-rated to 80 A for overload protection at site.
URI: http://10.1.7.192:80/jspui/handle/123456789/9405